vendor:
TAC Xenta 911
by:
Marek Cybul
7.5
CVSS
HIGH
Directory Traversal
22
CWE
Product Name: TAC Xenta 911
Affected Version From: 5.17
Affected Version To: 5.17
Patch Exists: Yes
Related CWE: N/A
CPE: a:schneider_electric:tac_xenta_911
Metasploit:
N/A
Other Scripts:
N/A
Platforms Tested: None
2018
TAC Xenta 511 and 911 Credentials Disclosure
Directory traversal in help manuals of Schneider Electric TAC Xenta 911 and 511 PLCs allows for credentials extraction. Devices are not indexed by crawlers like Shodan or Censys due to ancient SSL configuration, needed to use old browser to support it (not even s_client, curl or ncat could connect). Example URI: /www/help/public/../../../sys/pswd
Mitigation:
Upgrade to the latest version of the software and ensure that all security patches are applied.